Nothing on the walls. Every room on its own smart thermostat. Slim white PowerBoard panels on the ceiling warm people and everything in the room directly, instead of heating the air first. Supplied and installed across the UK.
250W integrated panel
750W surface panel
For your electrician
The electrical work
Circuits and contactors
Up to 12 × 250W or 4 × 750W panels share one 16 A thermostat circuit. A zone above 3,500 W switches through a contactor, with circuits sized by breaker: 5 × 750W on 20 A, 8 on 32 A.
Heights
The 750W face sits at least 2.3 m above the floor. Above 3.5 m we check the design and usually hang the panels on wires to bring the heat down. The 250W, at about 50 to 55°C, can go on ceilings from 1.8 m.
Clearances
50 mm to any surface or light fitting, 300 mm to curtains, shelving or anything that can burn, and never directly above or below stored materials. Never cover a panel, and never paint, tape or skim a 750W face.
Wiring and fixings
The 250W has a pre-fitted lead and connects with four-way adaptors, link cables and one cable back to the room thermostat. The 750W ships with its bracket and is wired by your electrician to our wiring specification. Screws are not supplied for either panel.
Thermostats
One electronic thermostat per room or zone, on an internal wall beside the door, 1.2 to 1.5 m up, out of the panel's direct radiation.
The full installation manual comes with the panels. For a copy before you order, call us free on 0800 342 3800.
The 250W integrated panel is boarded into the ceiling and skimmed over, so it suits a room where the ceiling is being replaced, and it is the panel for bathrooms and low ceilings. The 750W surface panel fixes to an existing ceiling on its bracket, so it suits finished rooms and larger spaces. Each design uses one panel type, sized from the room's heat loss.
Up to 12 × 250W or 4 × 750W panels on one 16 A thermostat circuit. Bigger zones switch through a contactor, and the circuits are then sized by breaker: 5 × 750W on a 20 A circuit or 8 on a 32 A circuit. Your design sets out every circuit.
The 750W face must be at least 2.3 m above the floor, because it runs at about 95 to 105°C. Up to 3.5 m is standard; above that we check the design and usually suspend the panels. The 250W runs at about 50 to 55°C and can go on ceilings from 1.8 m.
Only the 250W integrated panel is skimmed over, as part of the ceiling. Never paint, tape, plaster or cover a 750W surface panel, and never hang anything on or directly beneath it: keep curtains and anything that can burn 300 mm away.
No. The 750W panel is IP44 and we do not fit it in bathrooms. Bathrooms get the 250W integrated panel, which is IP54, placed in the ceiling where the design allows.
One electronic thermostat per room or zone, fitted on an internal wall beside the door, 1.2 to 1.5 m up and out of the panel's direct radiation. A zone above 3,500 W switches its panels through a contactor.
Send us the drawings or room sizes. We come back with the panel layout, the circuits and the running cost, from a free remote survey.